| A denial-of-service security issue exists in the affected product and version. The security issue is caused through CIP communication using crafted payloads. The security issue could result in no CIP communication with 1715 EtherNet/IP Adapter.A restart is required to recover. |
| Studio 5000 Logix Designer 30.01.00 contains an unquoted service path vulnerability in the FactoryTalk Activation Service that allows local users to potentially execute code with elevated privileges. Attackers can exploit the unquoted path in C:\Program Files (x86)\Rockwell Software\FactoryTalk Activation\ to inject malicious code that would execute with LocalSystem permissions. |
| A Local Privilege Escalation vulnerability exists in the affected product. The vulnerability requires a local, low privileged threat actor to replace certain files during update and exists due to a failure to perform proper security checks before installation. |
| CVE-2024-6078 IMPACT
An improper authentication vulnerability exists in the affected product, which could allow a malicious user to generate cookies for any user ID without the use of a username or password. If exploited, a malicious user could take over the account of a legitimate user. The malicious user would be able to view and modify data stored in the cloud. |
| A security issue exists within 432ES-IG3 Series A, which affects GuardLink® EtherNet/IP Interface, resulting in denial-of-service. A manual power cycle is required to recover the device. |
| An
authentication bypass vulnerability exists in the affected product. The
vulnerability exists due to shared secrets across accounts and could allow a threat
actor to impersonate a user if the threat actor is able to enumerate additional
information required during authentication. |
| A local code execution security issue exists within Studio 5000® Simulation Interface™ via the API. This vulnerability allows any Windows user on the system to extract files using path traversal sequences, resulting in execution of scripts with Administrator privileges on system reboot. |
| A local server-side request forgery (SSRF) security issue exists within Studio 5000® Simulation Interface™ via the API. This vulnerability allows any Windows user on the system to trigger outbound SMB requests, enabling the capture of NTLM hashes. |
| A security issue in the runtime event system allows unauthenticated connections to receive a reusable API token. This token is broadcasted over a WebSocket and can be intercepted by any local client listening on the connection. |
| A security issue exists within DataMosaix™ Private Cloud, allowing attackers to bypass MFA during setup and obtain a valid login-token cookie without knowing the users password. This vulnerability occurs when MFA is enabled but not completed within a 7-day period. |
| A security issue exists due to improper handling of malformed CIP packets during fuzzing. The controller enters a hard fault with solid red Fault LED and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF019. To recover, clear the fault. |
| A security issue was discovered within Verve Asset Manager allowing unauthorized read-only users to read, update, and delete users via the API. |
| A code execution security issue exists in the affected product. An attacker with physical access could abuse the maintenance menu of the controller with a crafted payload. The security issue can result in arbitrary code execution. |
| A vulnerability exists in the Rockwell Automation Emulate3D™, which could be leveraged to execute a DLL Hijacking attack. The application loads shared libraries, which are readable and writable by any user. If exploited, a malicious user could leverage a malicious dll and perform a remote code execution attack. |
| A security issues exists within Studio 5000 Logix Designer due to unsafe handling of environment variables. If the specified path lacks a valid file, Logix Designer crashes; However, it may be possible to execute malicious code without triggering a crash. |
| A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IY8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle. |
| A denial-of-service vulnerability exists via the CIP/Modbus port in the Rockwell Automation Micro850/870 (2080 -L50E/2080 -L70E). If exploited, the CIP/Modbus communication may be disrupted for short duration. |
| A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault. |
| A denial-of-service security issue in the affected product. The security issue occurs when a malformed CIP forward open message is sent. This could result in a major nonrecoverable fault a restart is required to recover. |
| A security issue was discovered within the legacy ADI server component of Verve Asset Manager, caused by plaintext secrets stored in environment variables on the ADI server. This component has been retired and has been optional since the 1.36 release in 2024. |